Chapter 5 Function parameter
61
Chapter 5
d0.28
Auxiliary frequency setting display
0.01Hz
Frequency set by F0.04 auxiliary frequency setting source
d0.29
Command torque (%)
0.1%
Display the set target torque under torque control mode
d0.30
Reserve
Reserve
d0.31
Synchro rotor position
0.0°
Current position angle of synchronous motor rotor
d0.32
Resolver position
-
Rotor position when rotary transformer is used as a speed feedback
d0.33
ABZ position
0
Displays AB phase pulse count of the current ABZ or UVW encoder
d0.34
Z signal counter
Displays Z phase pulse count of the current ABZ or UVW encoder
d0.35
Inverter status
Displays inverter running status information Data definition format is as follows:
Digit 1
0: stop; 1: forward; 2: reverse
Digit 10
Digit 100
0: constant; 1: acceleration; 2: deceleration
Digit 1000
Digit 10000
0: bus voltage normal; 1: undervoltage
d0.36
Inverter type
-
1:G type: Suitable for constant torque load
2:F type: Suitable for variable torque load (fans, pumps load)
d0.37
AI1 voltage before correction
0.001V
d0.38
AI2 voltage before correction
0.001V
d0.39
AI3 voltage before correction
0.001V
d0.40
Reserve
d0.41
motor temperature inspection function
0°C
Motor temperature sensor signal, need connect to control board S1 S2 GND terminal.
5-2-2.Basic function group: F0.00-F0.27
Code
Parameter name
Setting range
Factory
setting
Change
Limit
F0.00
Motor control mode
Vector control without PG
0
2
Vector control with PG
1
V/F control
2
0: Vector control without PG
Refers to the open-loop vector control for high-performance control applications typically ,
only one inverter to drive a motor.
1: Vector control with PG
Refers to the closed-loop vector control, motor encoder client must be installed , the drive
must be matching with the same type of PG encoder card . Suitable for high-precision speed
control or torque control . An inverter can drive only one motor.
2: V/F control
Suitable for less precision control applications, such as fan and pump loads .Oneinverter can
be used for several motors at the same time.
Note: When vector control mode , the drive and motor capacity can not vary widely.The
drive’s power can be bigger than motor’s power two degree or smaller than motors power one
degree.If not, it may result in not very good performance control, or the drive system does not
work normally .