Chapter 4 Installation and commissioning
24
External power
input terminal
To use an external signal when driving, connect PLC to
an external power supply and please unplug the PLC
jumper. Factory default is PLC jumper set to internal
+24V connection..
1.Input range: (DC 0V to 10V/0 to 20mA), depends on
the selected AI1 jumper on control panel.
2.Input impedance: 20kΩ with voltage input,
500
Ω with
current input.
1.Input range: (DC 0V to 10V/0 to 20mA), depends on
the selected AI2 jumper on control panel.
2.Input impedance: 20kΩ with voltage input,
500
Ω with
current input.
1. Input range: DC -10V to +10V
2. Voltage input impedance: 20kΩ;
3. AI3 reference potential can be GND or -10V.
Multi-function
digital input 1
1. Optocoupler compatible bipolar input, determined by
the setting of the jumper PLC;
2. Input impedance: 3.3kΩ
3. Level input voltage range is 19.2~28.8V.
Note: DI5 input impedance is 1.65k.
Multi-function
digital input 2
Multi-function
digital input 3
Multi-function
digital input 4
Multi-function
digital input 5
Multi-function
digital input 6
Multi-function
digital input 7
Multi-function
digital input 8
High-speed
pulse input
terminal
Except the function of DI1 to DI4, DI6 to DI8, DI5 can
also be used as high-speed pulse input channel.
Maximum input frequency: 100kHz
The selection of DA1 jumper on control panel determines
voltage or current output. Output voltage range: 0V to
10V, output current range: 0mA to 20mA
The selection of DA2 jumper on control panel determines
voltage or current output. Output voltage range: 0V to
10V, output current range: 0mA to 20mA
Opto-coupler isolation, bipolar open collector output
Output voltage range: 0V to 24V , output current range:
0mA to 50mA
Subject to function code (F2.00) "SPB terminal output
mode selection"
As a high-speed pulse output, the highest frequency is up
to 100kHz.
Contactor drive capacity: normally closed contact 3A/AC
250V, normally open contact 5 A/AC 250V, COSø = 0.4.
Normally closed
terminals