38
149.
F3.12
Braking utilization rate
0% to 100%
100%
150.
F3.13
Ac/deceleration mode
0: Linear acceleration and
deceleration
1:S curve acceleration and
deceleration A
2:S curve acceleration and
deceleration B
0
151.
F3.14
Proportion of S curve start-section
0.0% to (100.0%to F3.15)
30.0%
152.
F3.15
Proportion of S curve end-section
0.0% to (100.0% to F3.14)
30.0%
5-1-6.F4 Group - V/F control parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
153.
F4.00
V/F curve setting
0 to11
0
154.
F4.01
Torque boost
0.0% Automatic torque boost
0.1% to 30%
0.0%
155.
F4.02
Torque boost cut-off frequency
0.00Hz to F0.19(maximum
frequency)
15.00
Hz
156.
F4.03
MultipointV/F frequency point 1
0.00Hz to F4.05
0.00Hz
157.
F4.04
Multipoint V/F voltage point 1
0.0% to 100.0%
0.0%
158.
F4.05
Multipoint V/F frequency point 2
F4.03 to F4.07
0.00Hz
159.
F4.06
Multipoint V/F voltage point 2
0.0% to 100.0%
0.0%
160.
F4.07
Multipoint V/F frequency point 3
F4.05 to b0.04 (rated motor
frequency)
0.00Hz
161.
F4.08
Multipoint V/F voltage point 3
0.0% to 100.0%
0.0%
162.
F4.09
Slip compensation coefficient
0% to 200.0%
0.0%
163.
F4.10
Overexcitation gain
0 to 200
80
164.
F4.11
Oscillation suppression gain
0 to 100
0
165.
F4.12
V/F separation voltage source
0 to 9
0
166.
F4.13
V/F separation
voltage
digital setting
0V to rated motor voltage
0V
167.
F4.14
V/F separation voltage rise time
0.0s to 1000.0s
0.0s
5-1-7.F5 Group - Vector control parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
168.
F5.00
Speed loop ratio G1
1 to 100
30
169.
F5.01
Speed loopintegral T1
0.01s to 10.00s
0.50s

Table of Contents