Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-165-
corresponding function code.
P05.51
P05.52
Reserved
/
/
/
P06––Output terminals
Function
code
Name
Description
Default
value
Modify
P06.00
HDO output type
0: Open collector high-speed pulse output: Max.
frequency of the pulse is 50.00kHz. For details about
the related functions, see P06.27P06.31.
1: Open collector output: For details about the related
functions, see P06.02.
0
P06.01
Y output selection
0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: VFD fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running in zero speed
10: Reach upper limit frequency
11: Reach lower limit frequency
12: Ready to run
13: In pre-exciting
14: Overload pre-alarm
15: Underload pre-alarm
16: Simple PLC stage completed
17: Simple PLC cycle completed
18: Reach set counting value
19: Reach designated counting value
20: External fault is valid
21: Reserved
22: Reach running time
23: Virtual terminal output of Modbus/Modbus TCP
communication
24: Virtual terminal output of POROFIBUS /CANopen
communication
25: Virtual terminal output of Ethernet communication
26: DC bus voltage established
27: z pulse output
28: During pulse superposition
29: STO act
30: Positioning completed
31: Spindle zeroing completed
0
P06.02
HDO output
selection
0
P06.03
Relay RO1 output
selection
1
P06.04
Relay RO2 output
selection
5