Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-240-
P28––Master/slave control functions
Function
code
Name
Description
Default
value
Modify
P28.00
Master/slave mode
selection
0: The master/slave control is invalid
1: This machine is a master
2: This machine is a slave
0
P28.01
Master/slave
communication
data selection
0: CAN
1: Reserved
0
P28.02
Master/slave
control mode
0x000–0x112
Ones: Master/slave running mode selection
0: Master/slave mode 0
(The master and slave adopt speed control and
maintains the power balance by droop control)
1: Master/slave mode 1
(The master and slave must be in the same type of vector
control mode. The master is speed control, and the slave
will be forced to be in the torque control mode.
2: Master/slave mode 2
Start in the slave first speed mode (master/slave mode
0) and then switch to torque mode at a certain frequency
point (master/slave mode 1)
Tens: Slave start command source selection
0: Follow the master to start
1: Determined by P00.01
Hundreds: Slave transmitting/master receiving data
enable
0: Enable
1: Disable
0x001
P28.03
Slave speed gain
0.0500.0%
100.0%
P28.04
Slave torque gain
0.0500.0%
100.0%
P28.05
Master/slave mode
2 speed mode /
torque mode
switching
frequency point
0.0010.00Hz
5.00Hz
P28.06
Number of slaves
0–15
1
P28.07–
P28.08
Reserved
/
/
/
P28.09
CAN slave torque
offset
-100.0100.0%
0.0%
P28.10
Enabling
PT100/PT1000 to
detect temperature
0x00–0x11
Ones place: PT100 temperature detection
0: Disable
0x00