EasyManua.ls Logo

Sourcetronic ST600 - Page 15

Sourcetronic ST600
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quick Start Guide for ST600 Series Frequency Inverters Important Function Parameter Settings
14
P03.09
Current-Loop
Proportional
Coefficient P
0–65535
1000
P03.11
Torque Setting Method
0–1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDI
6: Multi-step torque
7: Modbus communication
0
P04.01
Torque Boost Of Motor 1
0.0%: (Automatic torque boost), 0.1%–10.0%
0
P04.09
V/F Slip Compensation
Gain Of Motor 1
0.0–200.0%
100.0%
P04.10
Low-Frequency
Oscillation Control
Factor Of Motor 1
0–100
10
P04.11
High-Frequency
Oscillation Control
Factor Of Motor 1
0–100
10
P05.01
Function Of S1
0: No function
1: Run forward
2: Run backward
3: Three-wire operating control (SIN)
4: Jog forward
5: Jog backward
6: Coast to stop
7: Reset errors
9: External error input
10: Increase frequency setting (UP)
11: Decrease frequency setting (DOWN)
1
P05.02
Function Of S2
4
P05.03
Function Of S3
7
P05.04
Function Of S4
0
P05.29
AI2 Lower Limit
-10.00V–P05.31
-10.00V
P05.35
AI2 Upper Limit
P05.33–10.00V
10.00V
P06.01
Y1 Output
0: Inactive
1: Running
2: Running forward
3: Running backward
4: Jogging
5: VFD in error
6: Frequency level detection FDT1
8: Frequency reached
0
P06.03
RO1 Output
1
P06.04
RO2 Output
5

Other manuals for Sourcetronic ST600