Quick Start Guide for ST600 Series Frequency Inverters Important Function Parameter Settings
15
P06.14
AO1 Output
0: Operating frequency
1: Set frequency
3: Rotation speed (Relative to the speed corre-
sponding to max. output frequency )
4: Output current (Relative to twice the VFD rated
current)
5: Output current (Relative to twice the motor rated
current)
6: Output voltage (Relative to 1.5 times the VFD
rated voltage)
7: Output power (Relative to twice the motor rated
power)
0
P06.16
HDO High-Speed Pulse
Output
0
P06.17
P06.21
AO1 Output
Upper/Lower Limit
Settings
For details, see the full version of the e-manual.
P07.00
User Password
0–65535
0
P07.27
P07.32
Present Error Type –
5th-Last Error Type
0–76
(0: No error)
For details, see the full version of the e-manual.
0
P08.28
Auto Error Reset Count
0–10
0
P08.29
Auto Error Reset Interval
0.1–3600.0s
1.0s
P14.00
Local Communication
Address
1–247
Note: The communication address of a slave can-
not be set to 0.
1
P14.01
Communication Baud
Rate
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
4
P14.02
Data Bit Check
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
1
P15.01
Module Address
0–127
2
P15.02
P15.12
Received Pzd2–
Received Pzd12
0–31
1: Set frequency (0F
max
, unit: 0.01Hz)
0