IM-P505-02-US Issue 1
19
UTM20 Series Ultrasonic Transit-time Flowmeters
Fig. 24
Note: Use suitably certified fittings/plugs to maintain the watertight integrity of the enclosure.
Generally, the right conduit hole (viewed from front) is used for power, the left conduit hole for
transducer connections, and the center holes are used for I/O wiring.
8. Install the wires through the gland nuts and connect the wires to the removable terminal blocks.
See “Wiring the Transmitter” on page 26.
9. Wire the transducers to the transmitter.
10. Plug the wired terminal blocks into the main board.
11. Reassemble the cover. Torque the cover screws to 45 in-lb.
12. Set up the meter. See “Initial Meter Setup” on page 41 for instructions.
½". NPT,
½". B S P P,
or M20 Threads
Ultrasonic Flow Meter