UTM20 Series Ultrasonic Transit-time Flowmeters
10.15 Setup > Communications
Requires service level passcode or higher if security is enabled For addressing information, see the
"UTM20 Meter Modbus RTU Protocol" user manual or the "UTM20 Meter BACnet MS/TP Protocol"
user manual, available at www.badgermeter com
An asterisk (*) indicates the parameter default
Communication Submenus Options/Descriptions
EIA-485 TYPE
DISABLE
*MODBUS RTU
BACNET MS/TP
Either disable this feature or select a network type
MODBUS RTU SETTINGS
(Displayed when MODBUS
RTU is selected as the
option for EIA-485 TYPE.)
ADDRESS Numeric entry 1 to 254
BAUD RATE *AUTO, 9600, 19200, 38400, 57600, 76800, 115200
ACCESS
WRITE/READ allows full access
RESET/READ allows you to read any, but only write to
Flow Total Reset (cannot set up meter)
READ ONLY allows read only
PARITY
*NONE
ODD PARITY
EVEN PARITY
STOP BIT
*1 STOP BIT
2 STOP BITS
RESISTOR
*DISABLED
ENABLED
WORD ORDER
BIG ENDIAN
*LITTLE ENDIAN
TIMEOUT Numeric entry 0 to 10000 ms
BACNET MS/TP SETTINGS
MAC ADDRESS Numeric entry 0 to 127
BACNET ID Numeric entry 0 to 4194303
BAUD RATE *9600, 19200, 38400, 57600, 76800, 115200
ACCESS
WRITE/READ allows full access
RESET/READ allows you to read any, but only write to
Flow Total Reset (cannot set up meter) READ ONLY
allows read only
MAX MASTER Numeric entry 1 to 127
PARITY
*NONE
ODD PARITY
EVEN PARITY
STOP BIT
*1 STOP BIT
2 STOP BITS
RESISTOR
DISABLED
*ENABLED