UTM20 Series Ultrasonic Transit-time Flowmeters
Communication Submenus Options/Descriptions
MODBUS TCP/IP
WEBSERVER
Note: WEBSERVER is READ ONLY
*ENABLED
DISABLED
CLIENT TIMEOUT 0 to 65,535 ms
WORD ORDER
BIG ENDIAN
*LITTLE ENDIAN
DHCP
*DISABLED
ENABLED
IP ADDRESS
Numeric entry ### ### ### ### Enter a value from 1
to 255 for the first value and 0 to 255 for the remaining
values Option not available if DHCP is enabled
SUBNET MASK
Numeric entry ### ### ### ### Enter each value
from 0 to 255 Option not available if DHCP is enabled
GATEWAY
Numeric entry ### ### ### ### Enter a value from 1
to 255 for the first value and 0 to 255 for the remaining
values Option not available if DHCP is enabled
DNS PRIMARY
### ### ### ### Enter a value from 1 to 255 for the
first value and 0 to 255 for the remaining values It
is not recommended to use static IP address in the
range of 169 254 0 0 to 169 254 255 255 because
clients may not be able to locate the DNS server
DNS
SECONDARY
### ### ### ### Enter a value from 1 to 255 for the
first value and 0 to 255 for the remaining values It
is not recommended to use static IP address in the
range of 169 254 0 0 to 169 254 255 255 because
clients may not be able to locate the DNS server
PORT
*AUTO NEGOTIATION
10 Mbit HALF DUPLEX
10 Mbit FULL DUPLEX
100 MbIt HALF DUPLEX
100 Mbit FULL DUPLEX
ACCESS
WRITE/READ allows full access
RESET/READ allows you to read any, but only write to
Flow Total Reset (cannot set up meter)
*READ ONLY allows read only