Rev. B 6-23-08 P/N S794
17
Section 2. Installation
Figure 10.
VENTING GUIDELINES
OUTDOOR INSTALLATION
Must be at least 3 ft. above any forced
air inlet located within a 10 ft. radius.
Vent Termination:
Must be located 6 in. away from the building wall,
and at the following distances away from
any door, window, or gravity air inlet:
4 ft. below,
4 ft. horizontally
Check local building codes
for setback requirements.
Force
Air Inlet
Property Line
4'
4'
6"
3'
SIDE VIEW
Building
Window
Exhaust
Grill
(Vent)
Exhaust
Grill
(Vent)
6 in.
4 ft.
Figure 11.
Must be at least 3 ft. (.9M) above any forced
air inlet located within a 10 ft. (3M) radius.
Vent Termination:
Must be located 6 in. (15.24cm) away from the
building wall, and at the following distances away
from any door, window, or gravity air inlet:
10 ft. (3M) below,
10 ft. (3M) horizontally
Check local building codes
for setback requirements.
Force
Air Inlet
Property Line
10'(3M)
6"
(15.24cm)
3'(.9M)
SIDE VIEW
Building
Window
Exhaust
Grill
(Vent)
Exhaust
Grill
(Vent)
6 in.
(15.24cm)
10 ft. (3M)
OUTDOOR INSTALLATION
VENTING GUIDELINES
FOR CANADA
10'(3M)