Piping:
Use at least 1-1/2" (38mm) IPS PVC pipe with 5” (127mm) trap. Use at least
2” (51mm) pipe with 6” (152mm) trap. Increase size if a long run is needed.
To avoid strains on the pump, support both suction and discharge pipes
independently. Place these supports near the pump.
To avoid a strain left by a gap at the last connection, start all piping at the
pump and run pipe away from the pump.
Never use a suction pipe smaller than pump suction connection.
To avoid airlocking, slope suction pipe slightly upward toward the pump.
NOTICE: To prevent flooding when removing pump for service, all flooded
suction systems must have gate valves in suction and discharge pipes.
Fittings:
Fittings restrict flow; for best efficiency use fewest possible fittings.
Avoid fittings which could cause an air trap.
Pool fittings must conform to International Association of Plumbing and
Mechanical Officials (IAPMO) standards.
Use only non-entrapping suction fitting or double suction.
5
TABLE I - RECOMMENDED FUSING AND WIRING DATA
P2RA Series
Motor Branch Fuse Max Load Voltage/ Dist. in Ft. (m) (Serv. to Motor)
H.P. Rating Amps* Amps Hz/Phase 0-100’ (0-30) 101-200’ (31-60) 201-300’ (61-90)
1/2 15 8.8 115/60/1 14 (2) 12 (3) 10 (5.5)
3/4 20 12.4 115/60/1 12 (3) 10 (5.5) 8 (8.4)
1 20 15.4 115/60/1 12 (3) 8 (8.4) 6 (14)
1-1/2 30 18.2 115/60/1 10 (5.5) 8 (8.4) 6 (14)
1/2 15 4.4 230/60/1 14 (2) 14 (2) 14 (2)
3/4 15 6.2 230/60/1 14 (2) 14 (2) 14 (2)
1 15 7.7 230/60/1 14 (2) 14 (2) 12 (3)
1-1/2 15 9.1 230/60/1 14 (2) 14 (2) 12 (3)
2 20 12.0 230/60/1 14 (2) 14 (2) 12 (3)
*Time delay fuses are recommended instead of standard fuses in any motor circuit.
P2R Series
Motor Branch Fuse Max Load Voltage/ Dist. in Ft. (m) (Serv. to Motor)
H.P. Rating Amps* Amps Hz/Phase 0-100’ (0-30) 101-200’ (31-60) 201-300’ (61-90)
1/2 20 12.4 115/60/1 12 (3) 10 (5.5) 8 (8.4)
3/4 20 15.4 115/60/1 12 (3) 8 (8.4) 6 (14)
1 30 18.2 115/60/1 10 (5.5) 8 (8.4) 6 (14)
1/2 15 6.2 230/60/1 14 (2) 14 (2) 14 (2)
3/4 15 7.7 230/60/1 14 (2) 14 (2) 14 (2)
1 15 9.1 230/60/1 14 (2) 14 (2) 12 (3)
1-1/2 20 12.0 230/60/1 14 (2) 14 (2) 12 (3)
*Time delay fuses are recommended instead of standard fuses in any motor circuit.