iQ Control Box
10 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC.
All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Table 3. Settings (continued)
Index Min
Value
Max
Value
Description Defaults
Single Dual
9 1 99 Close Torque Close Torque is the torque used during normal
operaon following the end of Close Startup Length.
This torque must be set to comply with BHMA/ANSI
door force equirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force. This torque seng is used in
conjuncon with Close Speed.
30 25
10 1 99 Close Check
Torque
Close Check Torque is the torque used during normal
operaon in close check state.
This torque must be set to comply with BHMA/ANSI
door force requirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force. This torque seng is used in conjunc-
on with close check speed.
35 25
11 0 2 Funcon
Switch Type
00 = Double pole rotary
01 = Rocker
02 = ICU
1 1
12 0 1 2S Operaon; 00 = 2S mode disabled / normal
01 = Push switch to open, push switch to close;
0 0
13 1 60 Close
Obstrucon
Time
Close Obstrucon Time is the amount of me in
increments of 0.025s the door applies force when
almost stopped or stopped when the controller
indicates a state of “07”.
Before increasing this parameter, check mechanical
issues, and speed and torque parameter sengs.
50 50
14 0 40 Open
Acceleraon
Open Acceleraon aects the rate at which the door
gets to its target speed.
This parameter is used when the door is lagging
open speed; open startup torque and open startup
length should be invesgated prior to increasing.
This parameter aects all open moon speeds: open
speed, open check speed, open learn speed, as well
as open braking.
30 30
Table 3 Settings continued next page.