Questions and Answers

  • G
    Gregory MiddletonAug 12, 2025
    What to do if I smell gas from my State Water Heaters SCE 80-115?
    • A
      Ashley AdamsAug 12, 2025
      If you smell gas, immediately close the main gas valve. Do not operate any switches and ensure there are no open flames. Ventilate the boiler room, and then contact your installer or local gas company.
  • K
    Kirk AlvaradoAug 20, 2025
    What to do if my State Water Heaters SCE 80-115 Water Heater is leaking?
    • S
      Shelley KimAug 20, 2025
      If you find water leaking from your State Water Heaters Water Heater, try these steps: * **Threaded Connection Leak:** Tighten the threaded connection. * **Leak from Another Source:** Trace the leak to identify its source. * **Tank Leak:** Consult the supplier and/or manufacturer. * **Condensation:** Wait until the water in the heater reaches the set temperature before drawing off too much hot water.
  • K
    Kaitlin HodgeAug 25, 2025
    Why is the power anode indicator lamp red or off on my State Water Heaters SCE 80-115 Water Heater?
    • K
      Kimberly DiazAug 25, 2025
      If the indicator lamp is red or off on your State Water Heaters Water Heater's Power Anode (optional), it could be due to: * Anodes not making contact with the water. * A break in one of the cables. * Anode poorly earthed. To resolve this: 1. Ensure the water heater is full of water. 2. Check the Power Anode is properly connected (see appendix ’A Electrical scheme SCE'). 3. Make sure all connections are properly made. 4. Check all cables for breaks and replace any if found. It could also be due to no power supply to the potentiostat. In that case, check the power supply.
  • R
    Richard LeachAug 27, 2025
    How to fix explosive ignition or poor flame on State Water Heaters SCE 80-115 Water Heater?
    • C
      chadstephensAug 27, 2025
      If you're experiencing explosive ignition or a poor flame profile with your State Water Heaters Water Heater, it could be due to: * Incorrect supply or burner pressure: Set the correct supply pressure and/or burner pressure (see ’3.11 Checking the supply pressure and burner pressure'). * Contaminated burner: Clean the burner (see ’9.4.2 Cleaning the burners'). * Contaminated orifice: Clean the orifice (see ’9.4.3 Cleaning the orifices'). * Inadequate air supply: Improve the air supply by better ventilating the boiler room.
  • B
    Brianna BennettAug 31, 2025
    What does it mean when the green light is ON but the red light is OFF on my State Water Heaters SCE 80-115 Water Heater?
    • S
      Sandra VargasAug 31, 2025
      If the green light is ON but the red light is OFF on your State Water Heaters Water Heater, there may be a blockage in the flue gas discharge. To resolve this, trace and remove the blockage, then reset the flue gas backflow safeguard (see paragraph ’5.8 Flue gas backflow safeguard reset button').
  • R
    Rebecca TorresSep 4, 2025
    Why are both the green and red lights OFF on my State Water Heaters SCE 80-115?
    • M
      Melissa AndersonSep 4, 2025
      If the green light is OFF and the red light is also OFF on your State Water Heaters Water Heater, it indicates no mains power is present. To address this: 1. Check that the mains switch is ON. 2. Check the voltage across the main switch. 3. Check the voltage on the electrical connector block. 4. Check the voltage on the burner control. 5. Check the fuse in the burner control. The measured voltage must be 230V AC +15% -10%.
  • A
    Andre BurnettSep 7, 2025
    Why is my State Water Heaters SCE 80-115 not producing enough hot water?
    • T
      Tina MaldonadoSep 8, 2025
      If you're getting insufficient hot water from your State Water Heaters Water Heater, it could be because the water temperature setting is too low. Set the control thermostat to a higher setting (see paragraph ’5.5 Control thermostat'). It could also be that the hot water supply has been used up. Reduce the rate of hot water consumption and allow the appliance enough time to heat up the water. If this occurs regularly, check whether the high-limit thermostat is cutting in/out and ensure the circulation- and/or shunt pump are working properly.
  • D
    Deanna GonzalezNov 15, 2025
    Why are both the green and red lights ON on my State Water Heaters Water Heater?
    • R
      robinsonemilyNov 15, 2025
      If the green light is ON and the red light is also ON on your State Water Heaters Water Heater, it could mean one of two things: * **(a) Three unsuccessful start attempts in a row:** Check that the gas valve is open, that the gas control opens (you should hear a clicking sound), and the gas control wiring. Also, check if the glow igniter lights up, its power supply and wiring. Finally, check the Phase (L) and Neutral (N) are correctly connected to the appliance and that the ionization rod and its wiring are correctly connected and not defective. * **(b) The safety thermostat has cut out:** Reset the appliance. Check whether the control thermostat and the high-limit thermostat are working. Also ensure the circulation pump (if present) is working. If the safety thermostat has cut out ...