Commissioning
11. Commissioning
11.1 Commissioning
Open a draw-off point until the appliance has filled up and
the pipework is free of air.
Adjust the flow rate. For this, observe the maximum permis-
sible flow rate with a fully opened tap (see chapter "Specifi-
cation / Data table"). If necessary reduce the flow rate at the
butterfly valve of the safety assembly.
Carry out a tightness check.
Turn the temperature selector to maximum temperature.
Switch the mains power ON.
Check the function of the appliance.
Check the function of the safety assembly.
11.1.1 Appliance handover
Explain the appliance function to users and familiarise them
with its operation.
Make the user aware of potential dangers, especially the risk
of scalding.
Hand over these instructions.
11.2 Recommissioning
See chapter "Commissioning".
12. Settings
12.2.1 Limiting the temperature selection
You can adjust the temperature selection limitation beneath the
temperature selector.
Factory setting: Limited to 60°C
Set the temperature selector to "cold" and isolate the appli-
ance from the power supply.
Remove the temperature selector and the control panel
cover.
1
2
26�02�79�0070
1 Limiter disc
2 Without limiter disc, maximum 82°C
You can set the limit to 45°C / 60°C by rotating the limiter
disc. After removing the limiter disc, the maximum tempera-
ture can be set.
Replace the control panel cover and temperature selector.
13. Shutting down
Disconnect the appliance from the mains at the MCB/fuse in
the fuse box.
Drain the appliance. See chapter "Maintenance / Draining the
appliance".