xxx Fault Effect Remedy
205
Maximum
outdoor air
temperature
exceeded
The high limit safety cut-
out may respond.
Isolate the appliance from the
power supply. Check the triac
for continuity. Check the sensor
cable.
—
Program-
ming unit
does not
start.
Parameters cannot be
adjusted.
I
2
C-connection faulty: Check cable
and plug-in connections. Replace
damaged cable.
Sensor resistance values
Note
When measuring with a multimeter, the resistance values
serve only to identify faulty or incorrect sensors. Measur-
ing with a multimeter is too imprecise to test for accuracy.
Sensor type
Supply air PT 1000
Exhaust air PT 1000
PT 1000
Temperature [°C]
-30 882
-20 922
-10 961
0 1000
10 1039
20 1078
25 1097
30 1117
40 1155
50 1194
60 1232
70 1271
80 1309
90 1347
100 1385
110 1423
120 1461