INSTALLATION
Power supply
12.2.1 Compressor and electric emergency/booster heater
Appliance damage
The compressor must only rotate in one direction. If the
fault NO POWER appears in the WPM3i display when the
compressor starts, change the direction of rotation by
interchanging two phases.
Appliance
function
Effect of the electric emergency/booster heater
Mono energet-
ic operation
If the heat pump cannot reach the dual mode point, the elec-
tric emergency/booster heater ensures both the heating oper-
ation and the provision of high DHW temperatures.
Emergency
mode
Should the heat pump suffer a fault that prevents its contin-
ued operation, the heating output will be covered by the elec-
tric emergency/booster heater.
Connect cables according to the following diagram.
D0000037506
X3 Electric emergency/booster heater (DHC)
L1, L2, L3, N, PE
Connected load Terminal allocation
2.9kW L1 PE
5.8kW L1 L2 PE
8.8kW L1 L2 L3 PE
X3 Compressor (HP)
L1, L2, L3, N, PE
12.2.2 Control voltage
D0000037507
X4 Control voltage (control outputs)
ON
KS
KUE
MKP
M(A)
M(Z)
HKP
UP
WW
Compressor signal
Brine pump signal
Cooling
Mixer circuit pump and N (X25), PE
Mixer open
Mixer closed
Heating circuit pump and N, PE
Pump
DHW
X4 Control voltage (control inputs)
L, L, N, PE Power supply
EVU Enable signal
!
Material losses
Do not connect a high efficiency circula-
tion pump directly to control output UP.
Use an external relay with a breaking capacity of at least
10A/250VAC or our relay set WPM-RBS.
If no voltage is applied to the power supply utility enable signal,
the heat pump will not start. The message “power-OFF” appears
on the controller. In this event, install a jumper across “EVU” and
phase “L”.