14. Settings
14.1 Standard settings
At the factory, the heat pump manager is programmed with the
following standard settings:
Switching times for heating circuit1 and2 (day mode)
only the 1stswitching pair is pre-programmed.
Standard Setting range
Monday - Friday 6:00 - 22:00 0:00 - 23:59
Saturday - Sunday 7:00 - 23:00 0:00 - 23:59
Room temperature 1 / 2
Standard settings without night setback.
Room temperature in day mode 20°C 5 - 30°C
Room temperature in night mode 20°C 5 - 30°C
DHW program switching times
Monday - Sunday 0:00 - 24:00 0:00 - 23:59
DHW temperature
DHW day temperature 50 °C OFF / 50 - 70°C
DHW night temperature 50 °C OFF / 50 - 70°C
Heating curve slope
Heating curve 1 0.6 0 - 5
Heating curve 2 0.2 0 - 5
14.2 Heating and DHW programs
You may enter your individual programs into the following tables.
14.2.1 Heating program, heating circuit 1
Switching time
pair I
Switching time
pair II
Switching time
pair III
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
14.2.2 Heating program, heating circuit 2
Switching time
pair I
Switching time
pair II
Switching time
pair III
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
14.2.3 DHW program
Switching time
pair I
Switching time
pair II
Switching time
pair III
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
14.3 Appliance handover
Explain the function of the appliance to users and familiarise them
with its operation.
Note
Hand over these operating and installation instructions
to the user for safe-keeping. Always carefully observe all
information in these instructions. They provide informa-
tion on safety, operation, installation and maintenance
of the appliance.