Parameter list software .112
d-- Defrosting control circuit 1
Para-
meter
Description of function Setting range Default
value
d0
Assignment of evaporation sensors (defrosting sensors)
detailed description of sensors in parameters H11 through
H53
0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from F1 and F2
2
d1
Defrosting interval 1...99 hrs. (0: no automatic defrosting) 8
d2
Type of defrosting 0: no defrosting
1: compressor off only (circulating air)
2: electrical
3:with hot gas
2
d3
Stop at defrosting temperature 0 ... +30.0°C 10.0
d4
Defrosting time limitation 1...99 min. 30
d7
Temperature difference to cold store setpoint in previous
cooling
-15°C ... 0.0°C 0.0
d8
Time limitation in previous cooling 1 ... 180 min. 10
d9
Delay of start of defrosting after compressor off d2=2
0 ... 900 sec. 60
d10
Dripping time 0 ... 15 min. 1
d11
Stop delay drip tray heating 0 ... 60 min. 10
d20
Display, forced release after defrosting 0 … 60 min. (0 = deactivated) 0
d99
Password of parameter level d--
-99 ... 999 0