Order number: 900323.001 V1.74 Page 8
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter list software .112
Para-
meter
Description of function Setting range Default
value
c7
Upper setpoint limit
c8...+99°C
50.0
c8
Lower setpoint limit
-99°C...c7
-50
c10
Start protection after compressor start 0 ... 900 sec. 300
c11
Start protection after compressor stop 0 ... 900 sec. 180
c12
Start protection compressor after mains on 0 ... 60 min. 0
c13
Additional condition:
compressor off if evaporator sensor < c13
-99 ... 50.0 °C -99
c14
Hysteresis for c13
0.1 ... 15.0 K 2.0
c15
On-time in emergency operation 0 ... 100% 50
c16
Cycle time in emergency operation 5 ... 60 min. 10
c20
Assignment of sensor for “super-frost” (also core or
product temperature)
detailed description of sensors in parameters H11
through H53
0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from F1 and F2
1
c21
“super-frost“: time limit
(“shock-frost”, “max. cooling power”)
1 ... 36 hrs. 10
c22
“super-frost“: temperature limit
(“shock-frost”, “max. cooling power”)
-40 ... 0°C 0.0
c23
“super-frost“: automatic off
(“shock-frost”, “max. cooling power”)
0: none, manual only
1: controlled by time
2: controlled by time or temperature
2
c30
Assignment of humidity sensor,
detailed description of sensors in parameters H11
through H53
0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from F1 and F2
0
c31
Humidity setpoint for Set1
c40c39
50%
c32
Night setpoint, humidity (relative to c31)
-20 … +20 % 0
c33
Humidity setpoint for Set2
c40c39
50%
c34
Humidity mode 0: off
1: evaporator fan on (continious operation)
2: Moisturize
3: Dehumidification with counter-heating
1
c35
Hysteresis humidity 0.1% … 15.0 % 5,0%
c36
Hysteresis mode humidity 0: symmetrical
1: one-sided
1
c37
Setpoint offset counter-heating for dehumidification
(relative to cold store setpoint c1/c2/c3)
-15.0 … 0.0 K -0,5
c38
Hysteresis for c37 (one-sided above)
0.1 … 10.0 K 1,0 K
c39
Upper setpoint limit c31/c33 c40 … 100%
100%
c40
Lower setpoint limit c31/c33 0,0% … c37
0,0%
c99
Password of parameter level c--
-99 ... 999 0