World Patents Pending ©AirSense Technology Ltd. 1999
ISSUE 2.4
Page 39
TECHNICAL. MANUAL
5. Reference
Setting of the reference time delay and reference back off for each detector is handled
in this menu.
6. Front panel
The front panel keys on a Stratos master can be individually enabled or disabled. Note
that disabling a key on the front panel of the Stratos master has the same effect on the
mimic, if connected.
7. Power monitoring
Battery check or mains check can be enabled or disabled. This may be necessary when
using an external power supply.
8. Air flow
Entering this menu is not possible if the flow is currently being set up. During flow set
up the aspirator is cycled through it’s different speeds and a note is taken of the flow
readings. The flow limits are set either side of this nominal value. This can be manually
changed in this menu if ‘tighter’ or ‘looser’ limits are required. The aspirator speed can
also be set up on this menu or a flow set up started.
9. Miscellaneous
This menu groups together all of those functions not covered by the other menus. The
chart recorder sampling rate, the access code or setting a default reset are set in this
menu.
10. Language
The Stratos has various languages built into it. In this menu, the required language is
prompted. Pressing Enter with no country code selected resets the detector language
back to English.