E/0204/39/39
Dehumidification with el. reheat
As above described, the dehumidification is obtained by reducing the fan speed and
simultaneous compressor operation.
An electric reheat is additionally operated, if the temperature difference to the cooling set point
exceeds a certain value below the set point.
Stop value
Dehumidification
(15°C)
Start value
Reheat
(22.5°C)
Dehumidification
Cooling
set point
(25°C)
Room temp.
Stop value
Reheat
Start value
Dehumidification