EasyManua.ls Logo

Stulz Split-Air CST 40 - Electrical Data; Split-Air CST 40; 50

Stulz Split-Air CST 40
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E/0204/39/8
CST 40 CST 50
Electrical Data Split-Air CST 40 / 50
Outdoor Unit
Power Supply Code
Nominal voltage
Tolerance on voltage
Phase
Frequency
Tolerance on frequency
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)*
Control voltage
Compressor
Power consumption*
Operating current (OA)*
Max. current (FLA)
Locked rotor current (LRA)
Condenser Fan
Power consumption*
Operating current (OA)*
Indoor Unit Type 1**
Voltage
Tolerance on voltage
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Evaporator Fan
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Indoor Unit Type 2**
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
Evaporator Fan
Power consumption*
Operating current (OA)*
Locked rotor current (LRA)
* Ambient temp. 35°C; Inside cabinet temp. 25°C RH 40%
** Type 1: with free cooling & emergency ventilation; DC fans;
Type 2: cooling only; with AC fans
00
230
220-240±10%
1
50
±2%
1.8
8.4
43.6
24
1.73
7.8
11.9
43
42
400
380-420±10%
3+N
50
±2%
1.8
4.2
22.6
24
1.73
3.6
5.4
22
V
V
ph
Hz
kW
A
A
Vac
kW
A
A
A
kW
A
VDC
VDC
kW
A
A
kW
A
A
kW
A
A
kW
A
A
00
230
220-240±10%
1
50
±2%
1.9
8.7
47.6
24
1.74
8.1
11.4
47
42
400
380-420±10%
3+N
50
±2%
1.9
3.8
24.6
24
1.74
3.2
4.2
24
0.11
0.58
24 / 48
22-28 / 43-56
0.13 / 0.13
6.1 / 3.05
9.25 / 5.42
0.1 / 0.1
4.82 / 2.42
8 / 4.8
0.18
0.82
2 x 0.7
0.18
0.82
2 x 0.7
0.11
0.58
24 / 48
22-28 / 43-56
0.25 / 0.24
11.75 / 5.66
17.25 / 10.22
0.22 / 0.21
10.5 / 5.04
2 x 8 / 4.8
0.19
0.83
2 x 0.7
0.19
0.83
2 x 0.7

Related product manuals