● FILTER CHANGE METER -The Filter Change Meter reset is located in the lower center of
the screen. Pressing the reset button will reset the hour meter to 0.0 from the time elapsed.
The change filter warning will be displayed when this meter reaches 6000 hours.
(Indicated in Figure 5B)
● Dew Point Common Alarm SP -The Service-Main screen also includes fields that allow
the setting of: Dew Point Common Alarm SP - This alarm should be set for the customer
required dew point high limit. (Indicated in Figure 5C)
● “LO SP" (low setpoint) - This is the dew point setting that puts the dryer in dew point
standby
● "Hi SP" (high setpoint) and Minutes - This is the dew point setting that brings the dryer
out of the dew point standby. Minutes - The setting in this field determines the maximum
time the dryer will stay in dew point standby. When this time expires (factory set 60 min) if
the dew point reading is still below the "LO-ST" the dryer will operate in the timed mode for
1-1/2 cycles prior to going back to the dew point standby mode. (Indicated in Figure 5D)
● Machine Run Meter- "Machine Run Meter" that is displayed in the Service-Main screen
and represents the dryer's operation time. This time is an accumulated operating time over
the life of the dryer. The hour meter cannot be reset. (Indicated in Figure 5E)
● MENU BUTTON- Pressing the Menu button will take the operator back to the Menu screen.