Section 1
SUPERVISOR PROTOCOL
4
The following messages are sent by the monitor:
MESSAGE TYPE FORMAT EXAMPLE
G - Get parameter ##Gn,xx 01G3,58
P - Change parameter ##Pn,v,xx 01P3,4,90
D - Display message ##Dxx 01D5B
I - Status info ##Ixx 01I56
A - Auto run mode ##Axx 01A5E
C - Cont run mode ##Cxx 01C5C
In the change parameter message n = number and v = value.
1 Machine type (read only)
2 Machine options (read only)
3 Language (0=French, 1=German, 2=Italian, 3=Spanish, 4=English)
4 Units (0=Metric, 1=English)
5 Unload pressure
6 Load pressure
7 P1 Max pressure
8 Off load time (0-15 min.)
9 Wye-Delta time (0-10 sec.)
10 Drain interval time (0-30 min.)
11 Drain time (0-10 sec.)
12 Restart time (0-60 sec.)
20 Machines (1 - 8)
21 Sequence method (0-Disabled, 1-Remote,
2-Slave, 3-Hours, 4-Com ID)
22 Sequence hours (0-30,000)
23 Lowest pressure
24 Recover time (2-30 sec,)
25 Capacity (0-10,000)
26 Rotate Time (10-250 hrs.)
40 T1 CAL (-7 to +7)
41 T2 CAL (-7 to +7)
42 T3 CAL (-7 to +7)
43 T4 CAL (-7 to +7)
44 T5 CAL (-7 to +7)
45 T6 CAL (-7 to +7)