Quarter -Turn Electric Valve Actuator【OM Series】 Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
6.3 Dip Switch Setting (SW1)
The Dip Switch SW1 is a combination of 8 switches and equally divided in two rows. It
is utilized to select signal type of input as well as output and fail positioning when the signal
input fails. The sliders can be placed at either ON (upper) or OFF (lower) state position.
Factory settings are switches 1, 4, 8 at ON state and switches 2, 3, 5, 6, 7 at OFF state.
a. Input signal setting (Switches 1 - 2)
Input 20 mA / 5 V / 10 V to operate valve to fully-open position
Input 20 mA / 5 V / 10 V to operate valve to fully-closed position
When signal input failed, driving valve to fully-open (when S6 sets at “ ON”).
When signal input failed, driving valve to fully-closed (when S6 sets at “ ON”).
When signal input failed, driving valve to fully-closed (when S6 sets at “ OFF”).
When signal input failed, driving valve to fully-open (when S6 sets at “ OFF”).
When signal input failed, valve stays at the last position.
Please follow steps below if an adjustment of these settings are required.
Please restart the actuator after adjusting.