Quarter -Turn Electric Valve Actuator【OM Series】 Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
6.4 Sensitivity Switch Setting (SW2)
When the sensitivity setting is higher, the resolution of the input signal will be higher, and
relatively the dead band will be smaller. Excessive high sensitivity setting may cause the
actuator to keep hunting and could not run to the desired position which will lead to the
thermostat inside the motor to trip because of overheating, and finally the actuator will shut
down. If this situation happens, it is suggested to turn down the sensitivity setting.
6.4.1 Setting
When switched to “1”: The Highest Sensitivity.
When switched to “0”: The Lowest Sensitivity.
6.4.2 Original Factory Setting
OM-1 to OM-13, OM-A, OM-AM, OM-H : 3.
OM-F & OM-G : 0
OM-1 to OM-13,
OM-H
OM-A, OM-AM
6.5 Signal Setting for Open and Close Position
These settings are set and calibrated at the factory. Mostly, they do not need to be
recalibrated. Please follow steps below to set when required.
Use a multimeter to measure the output signal in accordance with the selected signal
type.