Quarter -Turn Electric Valve ActuatorOM Series Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
21
The selection of the fail position while the input signal failed, please follow table
below:
Signal Failed Position
State of Switch
Fully-Open ( 90°)
7 at OFF, 8 at ON
Fully-Closed ( 0° )
7 at ON, 8 at OFF
The Last Position
7 at ON, 8 at ON
When S6 is set to OFF
The program defines 20 mA / 5 V /10 V as a command for fully-open
positioning. The line graph below shows the signal level and the corresponding
position of the actuator.
When a high signal value received, the actuator operates toward fully-open
position and when a low signal value received, the actuator operates toward
fully-closed position.
The selection of the fail position while the input signal failed, please follow table
below:
Input Signal
Fully-Open ( 90°)
Fully-Closed ( 0°)
4 - 20 mA
20 mA
4 mA
1 - 5 V
5V
1V
2 - 10 V
10V
2V
Signal Failed Position
State of Switch
Fully-Open ( 90°)
7 at ON, 8 at OFF
Fully-Closed ( 0°)
7 at OFF, 8 at ON.
The Last Position
7 at ON, 8 at ON.

Other manuals for Sun Yeh Electrical OM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sun Yeh Electrical OM Series and is the answer not in the manual?

Sun Yeh Electrical OM Series Specifications

General IconGeneral
BrandSun Yeh Electrical
ModelOM Series
CategoryController
LanguageEnglish