Quarter -Turn Electric Valve Actuator【OM Series】 Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
6.7.8 MODBUS Setting
MODBUS and modulating control cannot service at the same time.
MODBUS :
Set switches 1 - 2 at “ON” state and switches 3 - 8 at “OFF” state.
Baud rate setting
a. Press ”MODE” 2 times until displays.
b. Press ”SET” once, then will display.
c. Press ”DOWN” 10 times until displays.
d. Press and hold ”SET” around 3 sec until the LED indicator flashes to enter
setting mode.
e. Press ”UP” or ”DOWN” to set the required baud rate. (default value #4)
f. Press “SET” once to complete the setting.
Setting station
a. Press “DOWN” once, then will display.
b. Press and hold “SET” around 3 sec until the LED indicator flashes to
enter setting mode.
c. Press ”UP” or ”DOWN” to select the required station (Station Range:1 to
127, default Station: 1).
d. Press “Set” once to complete the setting.
Press ”Mode” 4 times to get back to the home page.