Operation Manual 10. Troubleshooting
59
When the grid voltage is below the min. LVRT normal voltage and the LVRT
function is enabled, this alarm information will be displayed
The short-time LVRT run alarm will be removed automatically when the grid
returns normal if this alarm is caused by grid fault. If this is a long-time LVRT run
caused by on-site low grid voltage, it is recommended to adjust the transformer
tapping voltage to increase the power yields.
During LVRT run, the active and reactive power follows the related LVRT
standard and does not follow the background dispatch.
Current transformer (CT) on the inverter control cabinet is abnormal
Check and service the CT on the measuring board when inverter is voltage-free
Inverter DC side insulation resistance is lower than the set value.
Check the PV panel insulation to the ground when the inverter is voltage-free
Only alarm display. The inverter can operate normally.
Functionality of the device internal cooling fan abnormal
Check the fan when inverter is voltage-free
Circuit breaker of the branch on the DC side is abnormal and this branch cannot
work normally
Check the abnormal circuit breaker when inverter is voltage-free
Before device stops, the non-abnormal branches can work normally and inverter
can operate in grid-connection normally
Inverter DC sensor abnormal
Check and service the DC sensor when inverter is voltage-free
After the anti-PID function is enabled, the panel positive resistance to the ground
is low due to customer's reason; or the power supply of the PID function module
is abnormal
Check the PID power supply when inverter is voltage-free