126
Parameters SH20T SH25T
Max. output current for back-
up load
3*63A
Backup data(off-grid mode)
Rated voltage 3 / N / PE, 220 / 380 V; 230 / 400 V; 240 / 415 V (± 2 %)
Rated frequency 50Hz / 60Hz (± 0.2 %)
THDV(@Linear load)
< 2%
Backup switch time
<10ms
Rated output power
20000 W / 20000 VA 25000 W / 25000 VA
Peak output power **
32000 W / 32000 VA,10s 36500 W / 36500 VA,10s
Rated output current for
backup load during on grid
mode
43000 W / 43000 VA (25℃)
Efficiency
Max. efficiency / European
efficiency
98.1% / 97.6 % 98.2% / 97.8 %
Protection & Function
Grid monitoring
Yes
DC reverse polarity
protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch (solar) Yes
Surge Protection DC Type II / AC Type II ***
PID Zero Yes
Parallel operation on grid port Master-slave mode
Battery input reverse polarity
protection
Yes
General Data
Topology (solar / battery) Transformerless / Transformerless
Degree of protection IP65
Dimensions (W x H x D) 620 * 480 * 245 mm
Weight 38kg 40kg
Mounting method Wall-mounting bracket
Operating ambient tempera-
ture range
-25 ℃ - 60 ℃
Allowable relative humidity
range(Non-condensing)
0% - 100%
Cooling method Natural convection Fan cooling
11 Appendix User Manual