- 26 -
E31
Water pressure switch fault
E32
Heating water temp. too high protection
E35
Compressor 1 high current protection
E36
Compressor 2 high current protection
E37
High temp. difference protection(water inlet and outlet)
E42
Cooling coil temp. sensor 1 fault
E43
Cooling coil temp. sensor 2 fault
E44
Low ambient temp. protection
E47
Heat recovery heat ex-changer 1 inlet temp. sensor fault
E48
Heat recovery heat ex-changer 2 inlet temp. sensor fault
E49
Heat recovery heat ex-changer 1 outlet temp. sensor fault
E50
Heat recovery heat ex-changer 2 outlet temp. sensor fault
E55
Communication fault (EEV control panel-PCB)
E56
Suction temp. sensor 3 fault
E57
Suction temp. sensor 4 fault
E58
Outdoor coil temp. sensor 3 fault
E59
Outdoor coil temp. sensor 4 fault
E60
Exhaust temp. sensor 3 fault
E61
Exhaust temp. sensor 4 fault
E62
Cooling coil temp. sensor 3 fault
E63
Cooling coil temp. sensor 4 fault
E64
High exhaust temp. protection 3
E65
High exhaust temp. protection 4
E66
Compressor 3 high current protection
E67
Compressor 4 high current protection
E68
High pressure switch 3 fault
E69
High pressure switch 4 fault
E70
Low pressure switch 3 fault
E71
Low pressure switch 4 fault
E72
Heat recovery heat ex-changer 3 inlet temp. sensor fault
E73
Heat recovery heat ex-changer 4 inlet temp. sensor fault
E74
Heat recovery heat ex-changer 3 outlet temp. sensor fault
E75
Heat recovery heat ex-changer 4 outlet temp. sensor fault
E80
Power supply fault ( 3 phases system, dial switch is 1 phase setting)
9. Adjusting and Initial operation
9.1 Attention
Within 12 hours after running, please connect the circuit breaker, and make the crankcase
heater be preheated.
Open the valve of water system, and the valve of assistant tank, inject water into the system,