Sussman Boilers:
ES, SSB & HU
Installation, Operation and Maintenance Manual
TABLE OF CONTENTS
Dimensional Information and
Component Identification . . . . . . . . . . . . . . . . . 2
Dimensional & Clearing Specifications. . . . . . . . . 3
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Installation
Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Pre-Operation Check. . . . . . . . . . . . . . . . . . . . . . . 10
Pressure Controls, Operation & Testing . . . . . . . 10
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Blowdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Timing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Optional Equipment . . . . . . . . . . . . . . . . . . . . . . . 14
Auxiliary Low Water Cut Off . . . . . . . . . . . . . . . . 14
Line Pressure Water Feed System . . . . . . . . . . . . . 14
High Pressure Water Feed System . . . . . . . . . . . . . 14
Condensate Return System . . . . . . . . . . . . . . . . . . 14
Vacuum Breaker Systems . . . . . . . . . . . . . . . . . . . 15
Automatic Blowdown System . . . . . . . . . . . . . . . . 15
Blowdown Separators . . . . . . . . . . . . . . . . . . . . . 15
Control Voltage Stepdown Transformer . . . . . . . . 15
Multistage Load Progressive Sequencers . . . . . . . . 15
Condensate Return Systems . . . . . . . . . . . . . . . . 16
Blowdown Separator Tanks . . . . . . . . . . . . . . . . . 17
Specification Charts . . . . . . . . . . . . . . . . . . . . . . . 18
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gauge Glass Installation . . . . . . . . . . . . . . . . . 20-21
Element Replacement . . . . . . . . . . . . . . . . . . . . . . 22
Water Quality Information
for Carbon Steel Boilers
. . . . . . . . . . . . . . . . . . 23
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Products covered by this manual:
Max
Series KW Range Steam Rate* BHP Design Pres.
Work Pres.
______________________________________________________________________
ES, HU 12-180 36-542 lbs/hr 1.2-18.4 0-100 psig 85 psig
SSB 12-180 36-542 lbs/hr 1.2-18.4 0-100 psig 85 psig
*Steam Rate- Steam @ 212 F with 50 F feed water
SSB Boilers have Stainless Steel all wetted metal parts. SSB
boilers shall be operated using only deionized water, having
a maximum conductance of 1 microSiemen per cm
(1
µS/cm) [minimum specific resistivity of 1 megohm per cm
(1
ΜΩ/cm)].
ES and HU boilers are of Carbon Steel construction.
See page 23 for Water Quality Information.
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500
1-800-238-3535 • Fax: (718) 937-4676 • email: seb@sussmancorp.com
www.sussmanboilers.com
Made in USA
PUR 101137 2/07
states a hazard which may
cause serious injury or
death if precautions are not followed.
signals a situation where
minor injury or product dam-
age may occur if you do not follow instructions.
IMPORTANT NOTE:
This highlights information that is especial-
ly relevant to a problem-free installation.
IMPORTANT NOTE:
As you follow these instructions, you will notice warning and caution symbols. This blocked information is important for the safe and efficient
installation and operation of electric boilers. These are two types of potential hazards that may occur during this installation and operation:
!
CAUTION
!
WARNING
Model No. ______________________
Boiler Serial No. _________________
National Board No. ______________
Safety Valve Set Pressure________
PSIG
Power Circuit Voltage ____________
Control Circuit Voltage ___________
Amps _____ Phase _____ HZ ______
IMPORTANT:
This data file contains the National
Board Registration Certificate approving your boiler.
It must be kept near the boiler at all times.
Question and Answer IconNeed help?

Do you have a question about the Sussman ES and is the answer not in the manual?

Summary

Safety Information and Warnings

Dimensional and Clearance Specifications

Clearance from Combustible Surfaces

Details required clearances around the boiler for safe operation and servicing.

Typical Wiring Diagrams

Control Circuit Wiring Diagrams

Illustrates the basic control circuit wiring for ES and SSB electric boilers.

Power Circuit Wiring Diagrams

SSB Manual Reset LWCO Wiring

Installation Requirements

Piping Installation Guidelines

Provides guidance for installing all piping in accordance with national and local codes.

Electrical Wiring Guidelines

Pre-Operation Checks

LWCO;Pump Control Testing

Step-by-step testing procedures for the low water cutoff and pump control system.

Pressure Control Testing

Explains how to check and set operating and high limit pressure controls.

Boiler Operation

Daily Blowdown Importance

Explains the importance of daily blowdown for boiler maintenance and longevity.

Boiler Maintenance Procedures

Routine Inspection and Checks

Details monthly inspections, checks for leaks, heating elements, pressure controls, and float controls.

Boiler Specifications

Boiler Sizing Guide

Gauge Glass Installation Guide

Gauge Glass Use and Care

Heating Element Replacement

Element Replacement Procedure

Step-by-step instructions for safely disconnecting, removing, and installing heating elements.

Water Quality for Carbon Steel Boilers

Recommended Feedwater Quality

Lists recommended quality parameters for feedwater supply to ensure optimal boiler performance.

Recommended Boiler Water Limits

Specifies acceptable limits for various impurities within the boiler water.

Limited Warranty Information

Sussman ES Specifications

General IconGeneral