33
Operation and maintenance instructions
Temperature
The temperature control can be congured as a supply air control or an extract
air control. By default, this function is congured as a supply air temperature
control. Changes to this conguration are done in the advanced setup; see
Section ..
Setting Settings
range
Factory
setting
T° heating 0...45°C 20,0°C
T° Cooling 0...99°C 24,0°C
T° Freecooling 0...99°C 15°C
Fire Alarm
An external re detection system is used to control the air handling unit in case
of emergency. The re alarm function is activated by means of digital input
IN.
Setting Settings
range
Factory
setting
Input Normally open
Normally closed
Normally
closed
Supply airow 0...max
Extract airow 0...max
Periodic maintenance
Built-in timer for maintenance warning; if the maintenance interval is
exceeded, a maintenance reminder will be displayed.
Setting Settings
range
Factory
setting
3 monthly warning Yes
No
No
12 monthly warning Yes
No
No
Commissioning completed
When the commissioning has been successful and this is conrmed in this
menu, the commissioning menu will not be activated automatically anymore.
Setting Settings
range
Factory
setting
Conrmation of
successful commis-
sioning
Yes
No
No
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
PERIODIC MAINTENANCE
PERIODIC MAINTENANCE
COMMISSIONING COMPLETED