36
Operation and maintenance instructions
Boost
The boost mode can be used to force the supply and extract
airow to a higher setpoint, when specic conditions are met.
The boost mode can be activated with a contact connected to
the digital input IN or by an analogue ...V control signal
connected to input K. The boost setpoint is preset in (l/s,
m³/h).
Setting Settings
range
Factory
setting
Supply / Extract airow 0...max
Boost activation on Contact
RH
Contact
RH on / o 0...100% 60% / 40%
Vmin/max RH on K3 0...10V 2,0V / 9,5V
RH ~Vmin/max 0...100% 2% / 95%
Post ventilation
The post ventilation function is used to keep the fans running
during a specied laps of time. This function is activated auto-
matically when an electrical heating coil is activated.
Setting Settings
range
Factory
setting
Activation No
Yes
No
Time 0...9999sec 90sec
DEACTIVATE SOFTSTOP
TEMPERATURE
BOOST
POST VENTILATION
EXTERNAL COILS
ADVANCED SETUP
TEMPERATURE
BOOST
POST VENTILATION
INTERNAL COILS
EXTERNAL COILS
ADVANCED SETUP