52
Operation and maintenance instructions
- Conditions:
•
Only with post-heating option.
- Causes:
•
For PX units:
Frost protection is only selected with electrical pre-heating coil (KWin) or water preheating coil (BAin) or modulating bypass.
With KWin or BAin option: In certain air T° conditions as measured on the exhaust airow aer heat recovery, indicating
that the internal electrical KWin coil or external hydraulic coil (BAin) has reached its limit, the TAC control can take
over to guarantee the anti-frost function.
If T° < assignment T°-1,5°C for more than 5 minutes: supply and exhaust airow reduction of 33% if airow control or
demand control and of 25%.
if pressure control mode, for 15 minutes.
•
For RX units:
When outdoor temperature (T1 sensor) is lower than the anti-frost temperature (T°AF, -9°C by default), the rotation
speed of the heat exchanger will decrease to avoid any risk of frosting.
When T1 ≥ T°AF for at least 5 minutes, the wheel will ramp up to its nominal rotation speed.
- Eects:
8.13 TYPE 13: ALARM INDICATING HEAT EXCHANGER FROST PROTECTION ALERT
TAC control board
ALARM OUTPUT AL dPa OUTPUT LED ALARM Fans
/ / ON /
Auto reset: yes
Displayed on HMI TACtouch
Code Text displayed Level
A.10 Anti-freeze - Reduced air ows 2