3
FIRE DAMPER - FD
PRODUCT OVERVIEW
DIMENSIONS
INSTALLATIONS
ACTUATORS
ACCESSORIES
REPLACEMENTS
MAINTENANCE AND OPERATION
PRODUCT OVERVIEW
TESTS AND
CERTIFICATES
All our dampers are submitted to a number of tests by official
test institutes. Reports of these tests form the basis for the
approvals of our dampers. Klimaoprema fire dampers are
also suitable for installation in buildings with high hygienic
demands such as hospitals, clinics and pharmaceutical areas.
To confirm this, our products are tested in independent Institute
of Hygiene, based in Gelsenkirchen, Ruhr, and comply with
directives and guidelines in VDI 6022.
FIRE RESISTANCE
CLASSIFICATION
FD fire resistance is tested according to EN 1366-2 “Fire
resistance tests for service installations- Part 2: Fire dampers”.
Classification of the fire dampers is defined according to EN
13501-3 Fire classification of construction products and
building elements.
Installation in both, vertical and horizontal axis of rotation of the
dampers blade is acceptable (with the axis in vertical or
horizontal).
Fire resistance of fire damper depends on classification of walls
or ceilings. It is allowed to install products to walls or ceilings
only according to products Declaration of Performance. Walls
or ceilings with greater fire resistance can also be used. Fire
damper should be installed according installation manual which
can be found within this document.
Please consult latest Declaration of Performance on our
website:
For more information about certificates, visit our website:
E - Integrity
I - Insulation
120/90/60 - Classification time in minutes
S - Smoke leakage
ve - Damper installed in vertical compartment
ho - Damper installed in horizontal compartment
i↔o - Fire performance criteria are met on both sides