38 sysmik.de Manual SCA-340 / SCA-340-L
4.4.3 Platform Service
The platform service (Sedona
App
service
plat) is a mandatory element of any
Sedona application and allows device specific configurations:
Timezonetime zone, e.g. Europe/Berlin
IP-Addressing
- Ip Addressingstatic or DHCP
- Ip Address
- Ip Net Masksubnet mask
- Ip Gatewaygateway address
- Ip Dns1, Ip Dns2, Ip Dns3Domain Name Server
Sntp AddressSNTP server address
Modbus TCP server
- Modbus Port (0 to deactivate Modbus server)
- Unit-ID
Modbus RTU
- Modbus Rtu Enabled
- Modbus Rtu Baud
- Modbus Rtu Parity
- Modbus Rtu Stop Bits
Niagara enabled in case the parallel operation of Niagara and Sedona is
not wanted, Niagara can be deactivated or again be enabled
IoPortTCP port number of the IO server
IoRemoteAddr to prevent an unwanted remote control of Scalibur IOs by
other Niagara stations, a remote control address can be configured. Default
is empty which blocks remote control completely. It is possible to allow
remote control only for a specific IP address by setting the entry to this
specific IP address. 255.255.255.255 allows remote control from any IP
address..
All configurations require a restart of the Scalibur to become effective.