Software
38 sysmik.de Manual SCA-340 / SCA-340-L
4.4.3 Platform Service
The platform service (Sedona
App
service
plat) is a mandatory element of any
Sedona application and allows device specific configurations:
Timezone – time zone, e.g. Europe/Berlin
IP-Addressing
- Ip Addressing – static or DHCP
- Ip Address
- Ip Net Mask – subnet mask
- Ip Gateway – gateway address
- Ip Dns1, Ip Dns2, Ip Dns3 – Domain Name Server
Sntp Address – SNTP server address
Modbus TCP server
- Modbus Port (0 to deactivate Modbus server)
- Unit-ID
Modbus RTU
- Modbus Rtu Enabled
- Modbus Rtu Baud
- Modbus Rtu Parity
- Modbus Rtu Stop Bits
Niagara enabled – in case the parallel operation of Niagara and Sedona is
not wanted, Niagara can be deactivated or again be enabled
IoPort – TCP port number of the IO server
IoRemoteAddr – to prevent an unwanted remote control of Scalibur IOs by
other Niagara stations, a remote control address can be configured. Default
is empty which blocks remote control completely. It is possible to allow
remote control only for a specific IP address by setting the entry to this
specific IP address. 255.255.255.255 allows remote control from any IP
address..
All configurations require a restart of the Scalibur to become effective.