Frequently Asked Questions and Answers
Q. Why is the product called the i
3
series?
A. The i
3
series represents a breakthrough in detection solutions, based upon three “I” principles: Installation ease,
Intelligence, and Instant Inspection. Installation ease is the result of the plug-in design, featuring the Stop-Drop ’N
Lock
attachment, efficient wire management, and in-line terminals, all intended to reduce installation time.
Intelligence refers to intelligent features provided such as a remote maintenance signal, drift compensation, and
smoothing algorithms. These features minimize the likelihood of nuisance alarms. Instant inspection refers to the
way in which the i
3
detectors’ sensitivity can be measured, as well as the red and green LED’s that readily indicate
the status of the smoke detector.
Q. What models are included in the i
3
series?
A. The i
3
series now offers a full-line of detectors and accessories to address a broader range of applications. They
include:
Detector Type Model Number
Two-wire standard 2W-B
Two-wire standard with 135° F thermal 2WT-B
Two-wire sounder with 135° F thermal 2WTA-B
Two-wire Form C relay with 135° F thermal 2WTR-B
Four-wire standard 4W-B
Four-wire standard with 135° F thermal 4WT-B
Four-wire sounder with 135° F thermal 4WTA-B
Four-wire Form C relay with 135° F thermal 4WTR-B
Four-wire sounder, with Form C relay, 135° F thermal 4WTAR-B
Four-wire isolated thermal, with sounder, Form C relay 4WITAR-B
Accessories
Model Number
Loop test/maintenance module 2W-MOD2
Reversing relay/synchronization module RRS-MOD
Sensitivity reader SENS-RDR
Removal/replacement tool RT
Retrofit adapter bracket A77-AB2
Q. How does the new isolated thermal model operate?
A. The i
3
isolated thermal detector, model number 4WITAR-B, operates similarly to the 2112/24AITR. Specifically,
when the detector’s photoelectric chamber detects smoke, only a local alarm indication is provided. Conversely,
should the detector’s thermal sensor be activated, a general alarm condition will result.
Q. Is the 2W-MOD no longer available?
A. The 2W-MOD was replaced by the 2W-MOD2. This new accessory accommodates all 2-wire standard, sounder,
and relay i
3
detectors.
Q. Can the original 2W-MOD be used with the new i
3
sounder or Form C relay models?
A. No. The 2W-MOD cannot be used with the new i
3
sounder and Form C relay models. However, the new 2W-MOD2
can be used on all i
3
detectors, both old and new.
Q. Can the other i
3
accessories be used with the new i
3
sounder or Form C relay models?
A. All other i
3
accessories may be used with the new i
3
sounder and Form C relay models. This includes the sensitivity
reader, removal/replacement tool, and the retrofit adapter bracket.
Q. What is the RRS-MOD and what are its functions?
A. The RRS-MOD serves two purposes. First, it activates all i
3
sounders on a loop when one goes into alarm, by
reversing the polarity of the power circuit. This allows the capability of installing multiple i
3
sounder models on a
loop. Second, the RRS-MOD synchronizes the output of all i
3
detectors on the loop, to ensure a clear audible
signal.

Other manuals for System Sensor i3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the System Sensor i3 Series and is the answer not in the manual?

System Sensor i3 Series Specifications

General IconGeneral
BrandSystem Sensor
Modeli3 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals