SS-300-022 1 I56-3936-002R
D4240 Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
TABLE OF CONTENTS PAGE
[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2]
Exploded View of Duct Smoke Detector Components
.............2
[3] General Description ......................................2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation .................................3
[7] Measurement Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Unit Configuration .......................................5
[10] Detector Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[11] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 6
[12] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Detector Cleaning Procedures ..............................7
[14] Sensor replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[15] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
BEFORE INSTALLING
Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct
Applications (A05-1004), which provides information on detector spacing,
placement, zoning, wiring, and special applications. This manual is available
online at www.systemsensor.com. NFPA Standards 72 and 90A should also be
referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
I56-3936-002R
SPECIFICATIONS
Operating Temperature: D4240: –4° to 158° F (–20° to 70° C)
Storage Temperature: D4240: –22° to 158° F (–30° to 70° C)
Humidity: 0% to 95% Relative Humidity Non-condensing
Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
D4240 Footprint Dimensions: Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)
Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)
D4240 Weight: 2.5 pounds; 1.14 kg
Electrical
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 240 VAC 50-60 Hz
Input capacitance: 270 µF max. 270 µF max. N/A
Reset Voltage: 3.0 VDC min. 2.0 VAC min. 20 VAC min.
Reset Time (with RTS451/RTS151): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec.
Reset Time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power Up Time: 35 sec. max. 35 sec. max. 35 sec. max.
Alarm response time: 15 sec. 15 sec. 15 sec.
Sensitivity Test: See detector label See detector label See detector label
Current Requirements (Using No Accessories)
Max. standby current 21 mA @ 24 VDC 65 mA RMS @ 24VAC 60Hz 10 mA RMS @ 240 VAC 60 Hz
Max. alarm current 65 mA @ 24 VDC 135 mA RMS @ 24 VAC 60 Hz 18 mA RMS @ 240 VAC 60 Hz
CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VDC (resistive)
Alarm auxiliary contatcs (DPDT) 10A @30 VDC (resistive)
10A @250 VAC (resistive)
1
/2 HP @240 VAC
1
/4 HP @120 VAC
NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of
control panels. Use the alarm initiation contact for this purpose.
Supervisory Contacts (SPDT) 2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY TROUBLE ALARM
APA151/APA451 12.5mA n/a 30mA Max.
MHR/MHW 0mA n/a 29mA Max.
RA400Z/RA100Z 0mA n/a 12mA Max.
RTS451/RTS151 0mA n/a 12mA Max.
RTS451KEY/RTS151KEY 12mA n/a 12mA Max.
SSK451/RTS2-AOS 8mA Max. 16mA Max. 40mA Max.
NOTE: Any combination of accessories may be used such that the given
accessory loads are: 110mA or less at the Aux output, and 50mA or less
at the Alarm output.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
[1] LIMITATIONS OF DUCT SMOKE DETECTORS
WARNING
The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The D4240 Air Duct Smoke Detectors
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual. Failure
to comply with these requirements may prevent the detector from activating
when smoke is present in the air duct.
Downloaded from Elcodis.com electronic components distributor
Question and Answer IconNeed help?

Do you have a question about the System Sensor InnovairFlex D4240 and is the answer not in the manual?

System Sensor InnovairFlex D4240 Specifications

General IconGeneral
BrandSystem Sensor
ModelInnovairFlex D4240
CategorySmoke Alarm
LanguageEnglish

Summary

LIMITATIONS OF DUCT SMOKE DETECTORS

DETECTOR INSTALLATION

VERIFY AIR FLOW DIRECTION AND VELOCITY

Ensures air velocity is within the detector's operating range.

DETERMINE MOUNTING LOCATION AND CONFIGURATION

Guides selection of mounting location and configuration type.

DRILL THE MOUNTING HOLES

Provides instructions for drilling mounting holes.

SECURE THE DUCT DETECTOR TO THE DUCT

Instructions on how to attach the detector to the duct.

SAMPLING TUBE INSTALLATION

SAMPLING TUBE SELECTION

Guides selection of the correct sampling tube length based on duct width.

SAMPLING TUBE INSTALLATION

Provides step-by-step instructions for installing the sampling tube.

MEASUREMENT TESTS

AIR FLOW MEASUREMENT

Verifies air speed and differential pressure for proper operation.

FIELD WIRING INSTALLATION GUIDELINES

WIRING INSTRUCTIONS

Explains how to make wiring connections using terminal strips.

SENSOR 2 INSTALLATION AND WIRING

Details how to install and wire a second sensor.

UNIT CONFIGURATION

DIP SWITCH SETTINGS AND FUNCTIONS

Explains configuration options using DIP switches and their functions.

DETECTOR STATUS INDICATION

LED STATUS INDICATIONS

Explains how to interpret the LED indicators on the detector.

INTERCONNECTION AND FAN SHUTDOWN

IMPORTANT INTERCONNECTION NOTES

Provides critical notes for interconnecting multiple units.

VERIFICATION OF OPERATION

FIELD SELECTABLE SETTINGS VERIFICATION

Verifies dip switch settings against Table 2.

POWERING THE UNIT

Instructions for applying power to the unit.

PERFORM DETECTOR CHECK

Guides a basic detector check.

DETECTOR CLEANING PROCEDURES

ALARM TESTS

Details how to perform alarm tests using buttons or accessories.

SMOKE RESPONSE TESTS

Explains how to test the detector's response to smoke.

DETECTOR SENSOR MAINTENANCE

DETECTOR SENSOR CLEANING

Step-by-step instructions for cleaning the sensor.

REINSTALLATION AFTER CLEANING

Steps for reinstallation after cleaning.

SENSOR REPLACEMENT (PART NO. 2 D51)

REPLACING THE SENSOR HEAD

Instructions for replacing the sensor head.

OPTIONAL ACCESSORIES

RTS451;RTS151;RTS451 KEY;RTS151 KEY REMOTE TEST STATION

Describes the functionality of the remote test station.

SSK451 MULTI-SIGNALING ACCESSORY

Explains the SSK451 accessory features.

RTS2;RTS2-AOS MULTI-SIGNALING ACCESSORY

Details the RTS2/RTS2-AOS accessory features.

THREE-YEAR LIMITED WARRANTY

Related product manuals