2.0 Performance Data
FULL LOAD
2.0 2.5 3.0 3.5 4.0 5.0
CFM
800 900 1200 1400 1500 1700
Total Cooling
Capacity *
24 30 34 40 45 55
Sensible Cooling
Capacity*
16.3 20.1 23.2 27.2 30.6 37.4
EER*
11.1 11.2 10.9 11.1 10.2 10.1
Heating Capacity**
24 29 34 40 45 57
COP**
3.5 3.4 3.5 3.3 3.4 3.3
PART LOAD
2.0 2.5 3.0 3.5 4.0 5.0
CFM
800 900 1200 1400 1500 1700
Total Cooling
Capacity*
18.5 24.5 27 33 37 41.5
Sensible Cooling
Capacity*
14.2 19.6 21.6 26.4 29.6 33.2
IPLV*
12.9 12.9 13.5 13.4 12.6 12.2
Heating Capacity**
20 25.5 29.5 35.5 39.5 46
COP**
4.1 4 4.2 3.9 4.1 3.8
Rated in accordance with AHRI Standard 390
* Cooling capacity rated at standard conditions- 80/67F indoor air, 95F outside air.
** Heating capacity rated at standard conditions- 70F indoor air, 47/43 outside air.
Rated in accordance with AHRI Standard 390
* Cooling capacity rated at standard conditions- 80/67F indoor air, 80F outside air.
** Heating capacity rated at standard conditions- 70F indoor air, 62/56.5F outside air.
2.1 Full Load
2.2 Part Load