Configuration |
17
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Heater
Choose heater type. Each selection unlocks additional configuration options. Default setting is based on unit type.
Available types: None / Electrical / Water / Change-over.
Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump temperature. Default setting is 10°C. This option is available if Water / Change-over heater
type is selected.
Range: 0–20°C.
Set circulation pump stop delay. Default setting is 5 minutes. This option is available if Water / Change-over heat-
er type is selected.
Range: Off / 1–60 min.
Cooler
Choose cooler type. Each selection unlocks additional configuration options. Default setting is None.
Available types: None / Water / Change-over.
Set outdoor air temperature interlock. Default setting is 10°C.
Range: 0–20°C.
Set actuator type. Default value is 0–10 V
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump stop delay. Default setting is 5 minutes. This option is available if Water / Change-over heat-
er type is selected.
Range: Off / 1–60 min.
Extra Controller
Choose extra controller type. Each selection unlocks additional configuration options. Default setting is None.
Available types: None / Preheater / Heating / Cooling / GEO Exchanger.
Set temperature set point of the extra controller. Default value is 0°C.
Range: –30°C 40°C.
Set P-band. Default setting is 4°C.
Range: 1-60°C.
Set I-time. Default setting is Off.
Range: Off / 1–240 sec.
Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump temperature. Default setting is 0°C. This option is available if Preheater controller type is
selected.
Range: 0–20°C.
Set circulation pump stop delay. Default setting is 5 minutes.
Range: Off / 1–60 min.
Bellow menus are available if controller type is selected as GEO Exchanger.
Pre-heater settings:
Set-point (-30 °C to + 10 °C).
Activation temperature (-30 °C to 0 °C).
Pre-cooler settings:
Set-point (10 °C to 30 °C).
Activation temperature (15 °C to 30 °C).
| v1

Other manuals for SystemAir SAVE VSR 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir SAVE VSR 300 and is the answer not in the manual?

SystemAir SAVE VSR 300 Specifications

General IconGeneral
BrandSystemAir
ModelSAVE VSR 300
CategoryFan
LanguageEnglish

Related product manuals