Possible Causes Possible Solutions
No display on the
wired controller
IDU is not powered on Power on the IDU.
Wired controller connection error
First power off the IDU, and then check if
the wired controller connection is correct.
See Section 3.4 on the wiring requirements.
Wired controller damaged Replace the wired controller.
Power supply failure of the IDU main PCB Replace the IDU main PCB.
E9
Wired
controller
and IDU
communi
cation
fault
IDU has no address or IDU address
duplicated
The
" "
icon in the wired controller is
always on.
Check if the indoor unit has been locked by
the centralized controller.
Table 8.1