32
Syscroll Air EVO HP 20 30
Power supply V/ph/Hz 400 ± ( 10%)/3+N/50
Maximum power input kW 13.2 15.8
Maximum current input A 25.9 30.9
Start-up corrent A 3.9 3.9
External fuses A 32 32
Max cable section (*) mm
2
10 10
HEAT EXCHANGER RESISTANCE
Power supply V/ph/Hz 230 ± ( 10%)/1/50
Maximum power input W 35
8 - Technical Data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum lenght of the power supply line.
8.3 Electrical data
8.3.1 Compressor electrical data
Syscroll Air EVO HP 20 30
Power supply V/ph/Hz 400 ± ( 10%)/3/50
Number 1
Maximum power input kW 11.9 14.4
Nominal current input A 15.0 20.0
Maximum current input A 22.0 27.0
Crankcase heater (230±(10%)/1/50) W 40
8.3.2 Fan electrical data
Syscroll Air EVO HP 20 30
Power supply V/ph/Hz 230 ± ( 10%)/1/50
Number 2
Maximum power input kW 0.3+0.3 0.3+0.3
Nominal current input A 1.3+1.3 1.3+1.3
8.3.3 Pump electrical data
Syscroll Air EVO HP 20 30
Power supply V/ph/Hz 400 ± ( 10%)/3/50
Number 1
Maximum power input kW 0.72 0.72
Nominal current input A 1.3 1.3

Related product manuals