55
3.1 HEAT MODE Enable or disable the heating mode
1 0 1 1 /
3.2 t_T4_FRESH_H
The refresh time of climate related curves for heating
mode
0.5 0.5 6 0.5 hours
3.3 T4HMAX
The maximum ambient operating temperature for heating
mode
25 20 35 1 ℃
3.4 T4HMIN
The minimum ambient operating temperature for heating
mode
-15 -25 15 1 ℃
3.5 dT1SH The temperature difference for starting the unit (T1)
5 2 10 1
℃
3.6
dTSH The temperature difference for starting the unit (Ta)
2 1 10
1
℃
3.8 T1SetH1
The setting temperature 1 of climate related curves for
heating mode
35 25 60 1 ℃
3.9 T1SetH2
The setting temperature 2 of climate related curves for
heating mode
28 25 60 1 ℃
3.10 T4H1
The ambient temperature 1 of climate related curves for
heating mode
-5 -25 35 1 ℃
3.11 T4H2
The ambient temperature 2 of climate related curves for
heating mode
7 -25 35 1 ℃
3.12 ZONE1 H-EMISSION
The type of zone1 end for heating mode :0=FCU(fan coil
unit),1=RAD.(radiator) ,2=FLH(floor heating)
1 0 2 1 /
3.13 ZONE2 H-EMISSION
The type of zone2 end for heating mode :0=FCU(fan coil
unit),1=RAD.(radiator) ,2=FLH(floor heating)
2 0 2 1 /
3.14 t_DELAY_PUMP
the time that the compressor has run before starting the
pump.
2 2 20 0.5 MIN
4.1 T4AUTOCMIN
The minimum operating ambient temperature for cooling in
auto mode
25 20 29 1 ℃
4.2 T4AUTOHMAX
The maximum operating ambient temperature for heating
in auto mode
17 10 17 1 ℃
5.1 WATER FLOW TEMP. Enable or disable the WATER FLOW TEMP.:0=NON,1=YES
1 0 1 1 /
5.2 ROOM TEMP. Enable or disable the ROOM TEMP.:0=NON,1=YES
0 0 1 1 /
5.3 DOUBLE ZONE
Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES
0 0 1 1 /
7.1 dT1_IBH_ON
The temperature difference betw een T1S and T1 for
starting the backup heater.
5 2 10 1 ℃
7.2 t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30 15 120 5 MIN
7.3 T4_IBH_ON The ambient temperature for starting the backup heater
-5 -15 10 1
℃
7.7 IBH_LOCATE
IBH/AHS installation location PIPE LOOP=0; BUFFER TANK=1
0 0 0 0
℃
7.8 P_IBH1
Power input of IBH1
0 0 20 0.5
kW
7.9 P_IBH2
Power input of IBH2
0 0 20 0.5
kW
7.10 P_TBH
Power input of TBH
2 0 20
0.5 kW
7.4 dT1_AHS_ON
The temperature difference betw een T1S and T1B for
turning the additional heating source on
5 2 10 1 ℃
7.5 t_AHS_DELAY
The time that the compressor has run before starting the
additional heating source
30 5 120 5 MIN
7.6 T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5 -15 10 1 ℃
8.1 T1S_H.A_H
The target outlet w ater temperature for space heating
w hen in holiday aw ay mode
25 20 25 1 ℃
8.2 T5S_H.A_DHW
The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode
25 20 25 1 ℃
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first
preheating for
floor
25 25 35 1 ℃
12.3 t_FIRSTFH The time last for preheating floor
72 48 96 12 HOUR
The style of room thermostat
:
0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
6.1
ROOM THERMOSTAT
0 0 3 1 /
3.7
t_INTERVAL_HEAT the start time interval of the compressor in HEAT mode.
5 5 5
MIN