Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
Manual/Auto
Inthismenutherunningmode
ofalltheconguredoutput
signalsandanumberofcontrol
functionscanbemanually
controlled.
Thesupplyaircontroller's
outputsignalcanbemanually
set(Manual/Auto)toanyvalue
between0and100%.The
temperatureoutputsignalswill
changeaccordinglyiftheyare
inAutomode.Itisalsopossible
tomanuallycontroleachof
thetemperatureoutputsignals
individually.
Sinceleavinganyofthe
outputsinmanualcontrolwill
disruptthenormalcontrol,
analarmwillbegeneratedas
soonasanyoutputissettoa
manualmode.
Supply
Temperature
contr.
Auto
Manualset:
0.0
Setthesupplyairtemperature
to"Auto","On"or"Off".
Settheoutputsignalbetween
0-100%.
TheoutputsY1,Y2andY3,if
inAuto-mode,willfollowthe
signalaccordingtothesetsplit
values.
SAF:Auto
Manualset:
0.0
EAF:Auto
Manualset:
0.0
SetthestartsignalforSAF
(supplyairfan)&EAF(exhaust
airfan)to"Auto,Manual
fullspeed,Manualhalf
speedorManual
Heating
Auto
Manualset:
100.0
SettheheatingtoAuto,
ManualorOff
Setthemanualoutput0-100%
Cooling
Auto
Manualset:
0.0
SetthecoolingtoAuto,
ManualorOff
Setthemanualoutput0-100%
Note:
Needstobeactivatedinorder
tobevisiblehere
P1–Heating
Auto
Setthepumpcontrolforthe
heatingcoiltoAuto,OnorOff
TA450-4500
OperationandMaintenanceInstructions
132616
15