EasyManua.ls Logo

SystemAir TA 4500 HW

SystemAir TA 4500 HW
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
P1–Cooling
Auto
Setthepumpcontrolforthe
coolingcoiltoAuto,OnorOff
Firedamper
Auto
SettheFiredampertoAuto,
OpenorClose
Note:
Needstobeactivatedinorder
tobevisiblehere
Congurationofredamper
functionsaremadeatSystem
level
Outdoorair
damper
Auto
SettheOutdoorairdamperto
Auto,OpenorClose
Settings
Inthismenugroupthesettings
fortheactivatedfunctionsare
available.Dependingonwhich
choiceshavebeenmadeinthe
congurationmenusomeofthe
possiblealternativesmaynot
bedisplayed.
Controltemp
Supplyair
control
P-band:
33.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
Roomcontrol
P-band:
100.0°C
I-time:300.0
sec
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinfo
Shutdownmode
P-band:
100.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
TA450-4500
OperationandMaintenanceInstructions
132616
16
SystemairSverigeAB

Other manuals for SystemAir TA 4500 HW