Pievienojums gaisa vadu sistēmai (Att. 3)
Nodrošināt visus savienojumus starp gaisa vadiem un T-gabaliem,
pievienojumiem, sašaurinājumiem u.c. izmantojot speciālu lentu vai 3
skrūves uz savienojumu. "Teleskopiskiem savienojumiem" uz Systemair
Zoom jābūt ar lentu.
Trokšņu slāpēšana (Att. 4)
Lai novērstu trokšņu pārnešanos uz telpām, jāmontē trokšņu slāpētāji (1)
pie pieplūdes/nosūces gaisa vadu pievienojumiem. L=1,0m.
Lai novērstu trokšņu pārnešanos starp telpām caur gaisa vadiem, kā arī
samazinātu troksni gaisa vadu sistēmā, trokšņu slāpētājus jāmontē pirms
katra pieplūdes difuzora (Att. 6).
Lokanie gaisa vadi (Att. 4)
Lokanos gaisa vadus (2) var izmantot tikai, lai savienotu iekārtu ar jumta
izmešanu un svaigā gaisa ieņemšanas resti.
Kondensāta/siltuma izolācija
(Att. 5)
Ārgaisa un gaisa sadales gaisa vadi vienmēr ir jāizolē pret kondensāta
veidošanos. Pareiza izolācijas montāža pie gaisa vada ir ļoti svarīga. Visi
gaisa vadi, kas iet caur aukstām, neapkurinātām telpām, jābūt kārtīgi
noizolētām. Jāizmanto izolācijas pārklājums (min. 50 mm minerālvate) ar
plastisko izkliedēšanās barjeru.
Reģionos ar ļoti zemām temperatūrām ziemas periodā, jāmontē papildus
izolācija. Kopējai izolācijas biezumam jābūt vismaz 100mm.
PIEZĪME! Pārliecināties, ka visi savienojumi ir pārklāti ar izolāciju un lentu
kārtīgi.
Duct connections (Fig. 3)
Secure all joints between ducting and Tee-pieces, duct connectors, reducers
etc. by means of special tape or 3 pcs. self drilling screws per joint. Always
tape the telescopic connections on Systemair Zoom ducts.
Attenuation (Fig. 4)
To avoid fan noise being transferred to rooms, install sound attenuators (1)
on connectors for inlet air and extract air on the unit. (L = 1,0 m).
To avoid noise being transferred between rooms via the duct system and
also to reduce noise from the duct system itself, installation of sound
attenuators before every inlet diffuser is recommended. (Fig. 6).
Flexible ducting (Fig. 4)
Flexible ducting (2) to be used only for connections between the unit and
roof unit / grill for fresh air intake.
Condensation/heat insulation (Fig. 5)
Fresh air duct and discharge ducts must always be well insulated against
condensation. Correct insulation installation on ducts connected to the unit is
especially important. All duct runs installed in cold rooms/areas must be well
insulated. Use insulation sleeving (50 mm mineral wool) with plastic diffusion
barrier.
In areas with extremely low outdoor temperatures during the winter,
additional insulation must be installed. Total insulation thickness must be
at least 100 mm.
NOTE! Make sure that all joints are covered with insulation, and tape well.