9
Diffuzori/Restītes
Pieplūdes, nosūces difuzori un virtuves nosūce (Fig. 6)
Pieplūdes difuzorus montēt visās dzīvojamās istabās, ēdamistabās un
guļamistabās. Nosūces difuzorus jāmontē dušas telpās, tualetēs, virtuvēs un veļas
mazgātuvēs. Nosūces difuzoru var tikt montēti griestos. Pieplūdes difuzorus būtu
vēlams montēt griestos. Pārliecināties, ka pieplūdes difuzora gaisam priekšā nav
šķēļu.
Gaisa plūsma no pieplūdes difuzoriem, kas montēti sienā (kur griesti ir horizontāli),
gaisa plūsmas garumam jābūt visu griestu garumā. Gaisa padeve caur nosūces
difuzoriem radīs gaisa plūsmu, un tādējādi nosūces difuzori var tikt izmantoti kā
pieplūdes difuzorus, ja tie tiek montēti sienā tuvu griestiem. Izmantot rāmjus
vieglākai difuzoru izņemšanai, lai iztīrītu gaisa vadus.
Pieplūdes difuzoru pamatiestādījumiem atvērt difuzoru pagriežot to 5 7 reizes no
aizvērta stāvokļa. Slēgt izmantojot centra asi. Pamatiestādījumi nosūces difuzoram
ir 10 apgriezieni no difuzora aizvērtā stāvokļa. Slēgt izmantojot centra asi.
Gaisa plūsmas iestādīšana
Gaisa ražības iestādīšana atsevišķām telpām jāveic saskaņā ar projektēšanas laikā
veiktajiem sistēmas aprēķiniem vai sistēmas palaišanas laikā (nepieciešams
speciāls mērīšanas aprīkojums).
DIFFUSERS/LOUVERS
Inlet diffusers, extract louvers and cookerhood (Fig. 6)
Mount inlet diffusers in all living rooms, dining areas and bedrooms. Extract louvers
to be installed in bathrooms, laundry room, WC and kitchen. Extract louvers can be
ceiling or wall mounted. Inlet diffuser should be mounted in the ceiling. Make sure
that the air stream from inlet diffusers has a free passage.
Air stream from inlet diffuser mounted on the wall (where the ceiling is horisontal),
must have throw length, so that the air is supplied to the room alongside the ceiling.
Air supply through extract louvers will ensure an air stream with throw length, and
extract louvers can therefore be used as inlet diffusers when mounted in the wall
close to the ceiling. Use frames to ease the removing of diffusers for cleaning.
For basic setting of inlet diffusers, open core of the diffuser 5-7 turns from closed
position. Lock by means of centre nut. For basic setting of extract louvers, open core
of the diffuser 10 turns from closed position. Lock by means of centre nut.
Setting of air volume
For adjustment of air volumes to each separate room, setting on diffusers/louvers are
to be made in accordance with calculations made during designing of the ventilation
system or during commissioning of the system (special measuring equipment
required).