Apollo Maxx User Manual
24
66
Charging current optimization
0-Disable
1-Enable
Default:0
(only in standby mode)
67
MPPT charger number
1~6
Step:1
Default:1
68
BGK_Module
For48V
0-N/A
1-BGK-12
For24V
0-N/A
1-BGK-Balancer
Step:1
Default:0
(Not lithium-ion batteries for
24V and 48V system)
69
BGK_RESTART
1 (Press <ENTER> to trigger
the effect once)
Default:0
70
Dry contact function
0-Default
1-User Define
Default:0
71
Dry contact 1 define
0- Ubat Low
1- OverLoad/OT
2- INV Fault
3- ACin Error
4- ACin Charging
5- ACin Ready
6- ACin Voltage>40V
7- Fan Running
Default:0
72
Dry contact 2 define
0- Ubat Low
1- OverLoad/OT
2- INV Fault
3- ACin Error
4- ACin Charging
5- ACin Ready
6- ACin Voltage>40V
7- Fan Running
Default:0